A walk-through of an electrical infrared report. The building, equipment and readings below are illustrative, but the layout and contents are what every client receives.

Sample, illustrative data
Electrical Infrared Inspection Report
Example Office Building, 100 Example Street
Report IR-0000
Scan date: example
Prepared by Isotherm Imaging

1. Summary

14 pieces of equipment scanned under normal load. 3 findings: 1 to repair immediately, 1 to repair as time permits, 1 to monitor.

2. Finding F-01, Panel LP-2, main electrical room

Illustration of a thermal image Three electrical connections seen by a thermal camera. The middle connection glows at 187 degrees Fahrenheit, 83 degrees hotter than its neighbor. 187°F 104°F Difference 83°F 190°F 130°F 70°F
Thermal image
B A C
Visible image
ComponentPhase B breaker, load-side terminal
Measured temperature187°F
Similar component (phase A)104°F
Difference83°F
Load at time of scanAbout 60% of breaker rating
SeverityPriority 1: repair immediately
Recommended actionDe-energize, inspect and re-terminate or replace the conductor and terminal. Rescan after repair to confirm.

3. All findings

IDLocationComponentDifferenceSeverity
F-01Panel LP-2Phase B breaker terminal83°FPriority 1
F-02Panel LP-2Neutral bar connection22°FPriority 2
F-03Switchboard MDPFeeder 4, phase A lug4°FPriority 3

4. Equipment scanned with no findings

Each item is listed by name and location, so the next scan covers the same equipment and the results can be compared year to year.

5. Conditions and method

Camera model and calibration date, emissivity and reflected temperature settings, ambient temperature, and the load on each circuit at the time of the scan.

6. Recommendations and next scan date

Repairs in order of priority, a rescan after Priority 1 repairs, and the date of the next annual scan.

How findings are rated

Severity is based on the temperature difference between a component and a similar component under the same load, following NETA maintenance testing guidance.

RatingDifference from similar componentAction
Priority 1More than 27°F (15°C)Repair immediately
Priority 27 to 27°F (4 to 15°C)Repair as time permits
Priority 32 to 5°F (1 to 3°C)Monitor; check at next scan